Pumping stations DIY relay repair

In detail: pumping stations do-it-yourself relay repair from a real master for the site my.housecope.com.

Sometimes the pumping station malfunctions. The water pressure in the pipeline decreases or the equipment stops functioning within the specified pressure limits. Often the reason for this situation is the failure of the pressure switch or violation of its settings.

Measurement and correction of pressure level

The pumping station is automated by means of a mechanical pressure switch. It controls the on and off of the pump, thereby maintaining a stable pressure in the water supply. If there are problems with this, it is necessary to measure the pressure level generated by the station and bring it in line with the standard settings.

Pumping equipment manufacturers usually set the following parameters:
• from 1.5 to 1.8 atm. - to turn on the pump;
• from 2.5 to 3 atm. - to turn off.

Before you start setting up the relay, you need to check the compressed air pressure in the accumulator tank. To do this, after disconnecting the station from power, open the tank lid (arrow in the figure). Then, using a conventional car pump with a built-in pressure gauge, we measure the pressure. Its level should be within 1.5 atm.

If the measured parameter is less than the specified value, it must be raised using the same car pump. It is advisable to carry out this procedure regularly. It is important that the air in the tank is under constant and equal pressure. This will ensure normal operating conditions for the accumulator and extend its service life.

After adjusting the pressure, the equipment should work normally. If the problems persist, you should start adjusting the relay settings. It should be remembered that the pump shutdown threshold cannot be set higher than the pressure level for which it is designed.

Video (click to play).

Adjustment of pressure switch settings

All configuration actions are performed when the station is in operating mode. Therefore, we connect the system to the network and wait for the pump to raise the pressure in the pipeline and turn off the engine on its own. Then you need to perform the following procedure:

1. After removing the relay cover, fully loosen the nut holding the smaller spring.

2. Set the minimum pressure level, upon reaching which the pump will turn on. This is done by rotating the nut of the larger spring.

3. Open the tap and drain the water. In this case, the moment the pump is turned on should be noted. If the value of this indicator is unsatisfactory, we repeat the adjustment procedure.

4. Set the pump off parameter. To do this, start the system and wait for the relay to activate. If its value is not satisfactory, we make the adjustment by rotating the nut of the small spring until an acceptable result is obtained.

If, after carrying out all the above actions, it was not possible to adjust the relay, most likely it is out of order. Then we are left with two options. Either replace the relay or repair it.

Imagine that you can simply turn on the tap to get water in the country. That it is not necessary to fill containers with buckets for basic hygiene procedures, cooking, cleaning. To do this, you just need to install pumping equipment with a pressure sensor, but first you need to figure out its device, do you agree?

Our article in fine detail will introduce you to a pressure switch for a pumping station. You will learn how the device works, how it activates and stops pumping.We describe in detail the popular options for pressure sensors and how to adjust them.

The author of the article lists the technological nuances and methods of setting the relay. This information is ideally complemented by useful diagrams, photo and video applications.

The device, small in size, belongs to the group of automatics serving pumping equipment. Its functionality is possible only in conjunction with a hydraulic accumulator. Despite its small size, the relay performs a number of important functions:

  • allows all devices to operate in a given mode;
  • responsive to changes in on / off thresholds;
  • activates and stops the pump when critical values ​​are reached.

Simply put, it regulates the automatic process of pumping water in independent water supply circuits with a membrane tank. The adjustment is carried out during the switching of electrical circuits when two pressure parameters in the system are reached, taken as the upper and lower limits.

Buying a pumping station, you get a set of equipment, part of which is a pressure switch. Externally, models of different brands and series are similar, but may differ in shape, size, body color, setting method and location. When self-assembling automation, it is necessary to study the characteristics of the devices and select the most suitable for a specific system.

The devices are adapted for convenient installation and maintenance of the pumping station. Most often, they are fixed with a union at the inlet of the accumulator, but they can also be mounted in the cold water system pipe in the immediate vicinity of the device.

The pressure control relay has a simple collapsible design, thanks to which the user can independently adjust the operation of the accumulator, narrow or expand the parameters.

The internal parts are arranged in a durable plastic case that resembles an irregularly shaped box. It has a smooth surface and only 3 external working elements: two sleeve clamps for electrical cables coming from the mains and the pump, and a ¼, ½, 1 inch metal branch pipe for connection to the system. The thread on the branch pipe can be both external and internal.

Inside there is a base to which the working elements are attached: large and small springs with adjusting nuts, contacts for connection, a diaphragm and a plate that changes its position depending on the increase / decrease of pressure parameters in the system.

The contacts of two electrical circuits, which are closed when the limiting pressure parameters are reached, are located under the springs, which are fixed on a metal plate. When the pressure rises, the membrane of the hydraulic tank deforms, the pressure inside the pear increases, the mass of water presses on the plate. That, in turn, begins to act on the large spring.

When compressed, the spring is activated and opens the contact, which supplies voltage to the motor. As a result, the pumping station is shut down. With a decrease in pressure (usually in the range of 1.4 - 1.6 bar), the plate rises to its original position and the contacts close again - the motor starts to work and pump water.

When buying a new pumping station, it is recommended to test the equipment to make sure that all components are working properly. Checking the performance of the relay occurs in the sequence described below. An example is the Haitun PC-19.

Mechanical models do not have an indication and control panel, but they can be equipped with a forced start button. It is needed to make the device function.

There are many universal models that are sold separately from the pumping stations and can be used to assemble the system yourself. When purchasing a relay or an automation unit, it is necessary to rely on the characteristics of the device. They can be found in the technical documentation.It is important that the capabilities of the relay match those of the rest of the equipment.

It should be based on the nominal pressure, but the upper limit of the working pressure is also important. Consider the electrical data and the maximum water temperature. The required parameter is the IP class, which denotes dust and moisture protection: the higher the value, the better.

Connecting thread sizes are indicated in inches: for example, ¼ "or 1". They must match the dimensions of the connection socket. The dimensions and weight of the devices themselves are approximately the same and are secondary characteristics.

It should also be remembered that there are built-in and detail models. Most of the commercially available devices are universal: they can be connected directly to the hydraulic tank or mounted on a pipe.

Electronic relays have the same functions as mechanical ones: they are responsible for the water supply and protect the pump mechanism from dry running. They are more capricious than simple models, and are sensitive to suspended particles in water. To protect the device, a strainer filter is installed in front of its connection.

One of the differences from the traditional model is the delayed shutdown of the pump. If, when the pressure rises, the mechanical device works quickly, then the electronic analogue turns off the equipment only after 10-15 seconds. This is due to the careful attitude to technology: the less often the pump is turned on / off, the longer it will last.

Some switch models, as well as automation units, work without a hydraulic accumulator, but their functionality is limited to simpler use. Suppose they are great for watering a vegetable garden or pumping liquid from one reservoir to another, but they are not used in the water supply system at home.

At the same time, the technical characteristics of the devices are the same as those of traditional relays: the factory setting is 1.5 atm., The shutdown threshold is 3 atm., The maximum value is 10 atm.

The collapsible design of the device and the setup instructions were not invented in vain. Factory parameters rarely meet the requirements of the water supply system, as well as the volume of the accumulator.

With the help of the setting, you can not only "adjust" the upper and lower limits to the optimal values, but also make the operation of the equipment more gentle - for example, reduce the number of pump starts / stops. To do this, it is enough to slightly increase the range between working pressures - delta.

You may also encounter an incorrect setting of the factory model. If the delta was incorrectly coordinated and made too small, then the pump will constantly turn on and off, responding to a minimum increase in parameters.

By manipulating the springs, you can achieve a change in the pump shutdown threshold, as well as adjust the volume of water in the accumulator tank. It is generally accepted that the larger the delta, the greater the volume of liquid in the tank. For example, with a delta of 2 atm. the tank is 50% filled with water, with a delta of 1 atm. - by 25%.

First, let's recall the general rules of adjustment:

  • to increase the upper limit of operation, that is, to increase the shutdown pressure, tighten the nut on the large spring; to reduce the "ceiling" - to weaken it;
  • to increase the difference between the two pressure indicators, we tighten the nut on the small spring, to reduce the delta, we loosen it;
  • clockwise movement of the nut - increase in parameters, against - decrease;
  • for adjustment, it is necessary to connect a manometer, which shows the initial and changed parameters;
  • before starting the adjustment, it is necessary to clean the filters, fill the tank with water and make sure that all pumping equipment is working.

All adjustment actions are carried out only after testing the system and detecting low performance or obvious errors in operation.It also happens that the station stops working due to a blockage that clogs the filter or one of the narrow pipes.

Let us examine the cases when it is really necessary to refer to the adjustment of the pressure switch. This usually happens when buying a new device or when there are frequent shutdowns of the pump. Also, adjustment is required if you got a used device with knocked down parameters.

At this stage, you should check how correct the factory settings are, and, if necessary, make some changes to the operation of the pump.

In order to follow the progress of the work, it is recommended to write down all the data obtained on a piece of paper. In the future, you can return to the initial settings or change the parameters again.

In this case, we forcibly turn off the pumping equipment and act in the following order:

  1. We turn on, and wait until the pressure reaches the maximum mark - let's say 3.7 atm.
  2. We turn off the equipment and lower the pressure by draining the water - for example, to 3.1 atm.
  3. Lightly tighten the nut on the small spring, increasing the value of the differential.
  4. We check how the shutdown pressure has changed and test the system.
  5. We set up the best option by tightening and loosening the nuts on both springs.

If the cause was a wrong initial setting, it can be solved without buying a new relay. It is recommended to regularly, once every 1-2 months, check the operation of the pressure switch and, if necessary, adjust the on / off limits.

There can be many reasons when the pump does not turn off or does not turn on - from blockage in communications to engine failure. Therefore, before you start disassembling the relay, you should make sure that the rest of the pumping station equipment is working properly.

If everything is in order with the rest of the devices, the problem is in the automation. We turn to the inspection of the pressure switch. We disconnect it from the fitting and wires, remove the cover and check two critical points: a thin connection pipe to the system and a block of contacts.

If the cleaning measures did not help, and the adjustment of the position of the springs was also in vain, most likely, the relay cannot be further used and should be replaced with a new one.

Suppose you have an old but working device in your hands. Its adjustment takes place in the same order as the setting of a new relay. Before starting work, make sure that the device is intact, disassemble it and check that all contacts and springs are in place.

Practical video tips will help you better understand how to adjust the new pressure switch of the pumping station if the parameters for some reason do not suit you. You will also learn how the dry running device is different.

Recommendations for setting up automation:

Professional advice for correct adjustment: