boiler Lemax floor, with two buttons, red and white. It stopped automatically starting, the wick is on, and it starts up when the gas regulator is set to zero, and then you raise the temperature and the boiler lights up, please tell me good people what could be the problem, otherwise we freeze at night.
wedges the rod in the middle of the automation.
my Lemax ksg-20d boiler with a gtu 24d burner goes out in the wind on the igniter. came from the gas service and changed the thermocouple all the time, and so on 3 times. tell me how to fix this malfunction?
it is necessary to increase the gas supply to the pilot burner, most likely when the main burner is turned on, the flame at the pilot burner decreases, which leads to the activation of the automatic protection. But one of the main reasons for this phenomenon is a decrease in gas pressure in the gas distribution system or, as mentioned above, the overturning of the draft in the chimney due to its incorrect installation.
Please tell me how many liters of water should be in the heating system for lemax ksg 20 mn, I have about 180m2 in the house and about 300 liters of water in the system. is it ok?
For 1 kW - 12-14 liters of water.
I purchased a gas boiler Lemax designed for 300 sq. eats gas all the time. Please tell me what could be the reason for this.
This phenomenon is observed if:
Video (click to play).
- The square of the heated area (300 m / sq) is equal to the power of the boiler (30 kW). Usually, the boiler is selected by 20 percent more in power than the heating area.
- If, with the above-mentioned area-power equalities, the heat carrier (water) is distilled by a pump, and not by gravity. The boiler simply does not have time to warm up this difference of 1-2 degrees (in the boiler itself, and not in the system, where the difference between the supply and return can reach up to 10 degrees) for the desired automatic operation, the volume of water that the pump drives.
In this case, the pump should be used only for a short time (3-5 minutes) to equalize the temperature at all heating points, and turn off the rest of the time. There are also nuances, but this is a more serious approach to this topic, where many factors and details are important and relevant.
boiler 2 years for 350 sq.m. in your own two-story house. specially bought a non-volatile cast iron, hoped to enjoy the winter and now in the off-season heat in the house. As spring or autumn comes, it goes out 20 times a day, but now I sat next to it for 2 hours, I can’t light it up, I’m tired of holding the igniter button, there the gas does not enter the burners at all. We bought it on our own head, it was necessary first to really read the reviews.
The whole problem is in the traction sensor, or rather in the connectors, you take it off or move it and the boiler starts working.
8 years ago I installed myself a Lemax Ksg-7.5 boiler. The first 3 years worked flawlessly, then problems with ignition began, tk. the boiler goes out constantly. The traction sensor, overheating was turned off. Now also email. the solenoid valve is broken. And generally I don’t understand, couldn’t it be more convenient to make the ignition button, when you light it up for 2 hours - you don’t feel your fingers.
just like that the boiler does not turn off, you need to look for the reason, if you are sure that the magnetic valve is broken, then replace it, and the draft sensor was turned off in vain.
Lemax KSG-12.5D boiler (GGU-15D burner). it went out sharply, it did not work out again. What to do, what is the reason?
Most likely, the pilot (pilot) burner jet is clogged. It is necessary to unscrew the thermocouple nut (located to the right of the igniter), take it to the side, unscrew the igniter tube nut, take the tube aside to get the nozzle, blow it out.
Lemax KGS-16D, the amount of coolant is up to 240 liters, when I bought it I thought it would work fine. I would have known that it would be so, the KChM would not have touched. Why then, if it is difficult for Lemax to push CO, it does not throw water through the air tube into the expansion tank, it works without any noises and knocks, heats itself up to 90g and is cut down, cools down a little and works again. And at the exit 60gr.
Turn off the thermostat, then the water fountain. About 240 liters. Will work fine. but with a pump it will be noticeably more economical than KChM.
Gas boiler Lemax, ignition system Sit 710, when the ignition button is released, the wick goes out, What should I do? Shorted the sensor with two wires outside. It works. Can I leave it like that?
nine out of ten boilers operate with shorted thermocouples. In theory, yes, this should not be done, it is dangerous. Because if the gas supply is cut off, the thermocouple must disconnect and shut off the gas supply, thereby preventing leakage. In practice: a thermocouple burns out on the wick very quickly (because they have a very poor-quality soldering), even for a season they do not have enough, it is sometimes quite difficult to buy a new one, and it is expensive.
Tell me from what the boiler can turn off by itself. This happens especially often in bad and windy weather. How can this be fixed?
After ignition of the igniter, the emk should work in 15-20 seconds. After the igniter goes out, the emk is turned off (a click is heard) - at least 10-12 seconds.
Tell me why, when the burner turns off and only the igniter is on, the fire is knocked out forward - so that there is a danger for the gas burner device, because the fire is burning directly under it?
Because there is no thrust. The channels in the heat exchanger may be clogged with soot.
Tell me, please, here we have a Lemax boiler, since 2009, we bought a new one. All this time, the huge problem is to light it up. When ignited, when you release the button, the wick immediately goes out. We tried to hold the button for a long time. Nothing helps. Sometimes you have to kindle for several hours to ignite the wick. foremen from the gas service said that these were some kind of contacts. they didn't explain or fix anything. What to do?
It is necessary to turn off the draft sensor, which is located at the back of the boiler, and problems should not arise. Check if the protection works in the event of a gas cutoff, the protection should work and the boiler will shut down. The sensor is located at the top of the back or on the gas burner itself.
The Lemax boiler does not turn on, what should I do?
The thermocouple contacts may have acidified or the thermocouple has burned out. You need to clean the contacts or replace the thermocouple.
There is a gas boiler Lemax KSG-10 automatic MiniSit. There was always a problem with ignition, there you need to press a large button, light the wick and slowly release the button, and at this time the igniter goes out, very strong nerves are required to release this button slowly, slightly twitched and the valve cuts off the gas, the igniter goes out.
During the ignition, I close the contacts directly on the automation, these contacts go to the draft sensor, when the boiler flared up and reached the temperature after 20 minutes, I removed the jumper and the automation worked as usual, but something broke and now the boiler goes out when I remove the jumper, I tried to replace this traction sensor, it turned out to be a regular thermostat, I had it at 110 degrees, I did not find one, I found it at 120, and then at 95, there is no effect from the replacement.
It is scary to operate with a closed jumper, because if it dies out from the wind or something else the valve does not work, I checked it. Something tells me that it is automatic, and not this sensor. What do you think?
To determine the malfunction, you need to do several checks:
- Check how the pilot is heating the thermocouple. The flame should wash well at the working end.
- Are the air injection holes in the pilot burner clean?
- Is the contact between the terminals and the wires secure? The best part is soldering.
- Check if the adapter is well tightened near the gas valve, where the wires and thermocouple come from.
The 710 minisit valve generally works without breakage. Also during operation, the holes may become clogged, which must be cleaned.
Lemax K-Plus boiler, when the boiler is started, an E5 alarm periodically occurs, but the boiler does not go into an accident, but continues to work, but after several restarts, an E9 error appears, constantly repeating E5. The board was changed, the pneumorel was also changed. What could be? In the stabilizer, the phase is through, the stabilizer is autotransformer.
Measure the voltage on the contacts of the pressostat themselves and on the board, perhaps the problem is in bad contacts. And there should be zero throughput, and in phase - regulation.
I have a new Lemax-10 boiler. There is only one problem - it periodically goes out and goes out. They came from the gas service - sang something about a bad chimney, like you need to solve the problem there first, and left. There may of course be a problem in the chimney, but the old AOGV boiler has worked for 23 years with this chimney. Friends, what is the reason for this behavior of the boiler, what should I do?
First, check your cravings. It is possible that when burning, the flame simply does not hit the thermostat, the automation thinks that the flame has gone out and turns off the gas. This error often occurs due to mechanical damage or clogging of the nozzle.
Boiler "Lemax" Taganrog. Danko automatics. I cannot light the boiler. The wick goes out after releasing the button, no matter how long you keep it pressed. The thermocouple is washed by a flame, there is a thrust, and the gas pressure is sufficient. Contacts are recommended to be cleaned. Help with advice, please. When I release the start button, a faint metallic click is heard when the flame is extinguished.
A question for the Eurosit630 specialists - should the automation, with normal setting, increase the power when turning by large divisions linearly or not? for me - from almost 3 and above, the division goes to the maximum. no linear power increases, and even the automation itself is not observed.
Perhaps the reason is in the traction sensor - it is poorly fixed. You can solder wires to the sensor instead of the removable pins and fix them.
Heating water-heating boiler LEMAX KSG-7,5 with "Comfort" automatic equipment. The water temperature gauge is working, the thermostat knob is working, the batteries are evenly heated. But AUTOMATICA did not start working on the thermostat, it stopped switching off periodically. I cannot understand the reason.
It can be assumed that when the boiler is operating, when the water temperature reaches the set value, the main burner does not switch to the “low gas” operating mode. The solution to the problem is to replace the “bellows-thermocylinder” thermosystem.
for five years the boiler lemax ksg12 stood, area 30 sq. m, the consumption is small, but the water temperature is not more than 60 burns incessantly two batteries of medium 14 sections, how to make it warmer, how to raise the temperature in the boiler?
in severe frosts, the pressure in the gas line drops, respectively, less gas is supplied to the boiler than is required, from this and the temperature of the coolant is less than the specified one. Installing a circulation pump can also help.
According to safety rules, the repair of all equipment dangerous in operation, which includes gas heating units, must be carried out by specially trained qualified specialists. However, in remote areas, the arrival of a specialized repair team can be expected for a very long time. Therefore, in case of emergency, if the matter does not concern automation and the gas pipe, you can do it yourself and repair the gas boiler yourself.
Modern gas heating systems are complex systems.Control of their work is carried out using a whole range of automatic devices, which must be familiarized with before starting an independent repair of gas boilers.
The main elements of the security group:
Draft sensors designed for 75 0 C. This device makes it possible to monitor the state of the chimney. If the normal flue gas discharge fails, the temperature rises and the sensor is triggered. Optimally, in addition to the traction sensor, a gas alarm is acquired.
The monostat protects turbocharged gas units from impaired removal of combustion products due to a clogged chimney or heat exchanger.
The limit thermostat is designed to control the temperature of the heating medium in the heating system. When the water boils, the overheating sensor turns off the device.
When the flame is detected, the flame control electrode switches off the operation of the heating unit.
A blast valve is used to control pressure. With an increase in pressure above the critical value, a portioned discharge of excess coolant occurs.
Attention!The wear of the stuffing box leads to a constant flow of the coolant from the valve. The remedy is to replace the valve.
Various components of the heating system can fail and for various reasons. It can be - low-quality parts, violation of the requirements for operation, sharp blows to the component parts of the unit.
The most common reason for the failure of volatile devices is a configuration failure. Do-it-yourself gas boiler repair should begin by checking that the settings are correctly installed and the presence of open contacts. When troubleshooting, the unit is set to the "Winter" mode and the setting is set to the maximum heating temperature.
If the pump does not work, then either you just need to replace the cable, or you will have to change the pump itself.
If the burner is not supplied with gas, then it is necessary to make sure that the gas valve is open, the gas line is not clogged, the voltage supply is in order. If the problem persists, after all these steps, you will most likely have to change the electronic board.
The shutdown of parapet boilers in severe frosts can be caused by the appearance of ice on the chimney. The formation of an ice crust is explained by the content of water vapor in the exhaust combustion products. As a result of freezing of ice build-up and obstruction of the exit of flue gases, the device is automatically turned off and attempts to turn it on again will be unsuccessful.
Advice!In this case, the automation of the boiler equipment does not fail, and to resume the operation of the heating equipment, it is enough to remove the ice from the smoke grate. In order to avoid such stoppages of the units, it is necessary to periodically inspect the chimney in severe frosts.
Do-it-yourself gas boiler repair is not always possible and only in cases of visible and simple malfunctions. Complex breakdowns can be corrected efficiently and reliably only by specialists with the necessary knowledge and equipment.